2016 USER QUESTIONS - SmartZone Advanced

Support, homeownerszoning supplyComment
Photo by BackyardProduction/iStock / Getty Images

QUESTION: I have two 9580 thermostats one in the office, the other in the main hangar bay (two zones).  When heating both zones or only the hangar, I need the furnace to go full blower with normal scheduling through stages 1 and 2.  When servicing only the small office area, I don't want the system to advance from stage 1.  Unfortunately, the office is so small and the modulating schedule of the furnace is still too much airflow for the office (the zone bypass when servicing the office is the main hangar modulating damper that is controlled via SPC (excess dumps into hangar)).  This damper will be wide open during call for hangar heat.  The main damper control logic is managed through a 3PDT  24 Vac relay. So, I need to block out stage 2 from only 1 zone (office).  The zone ramping schedule of the 9580 works well with the 100k modulating furnace control board, and would like to keep that capability. 

ANSWER: Configure the zone 1 thermostat connector STAT TYPE to G2 (conventional gas/electric) or H2 (heat pump) to allow the thermostat to control staging and use the hangar thermostat on zone 1. Wire only the stage 1 circuits (Y1 and W1) on the office thermostat to the zone 2 thermostat connector (Also connect R, C and G wires). Set dipswitch 4 to the LOCKOUT position. This will configure the zone controller to allow 2nd stage only when the hangar thermostat calls for 2nd stage regardless of whether the office thermostat is calling. When the office thermostat is calling and the hangar thermostat is not, SmartZone will not allow 2nd stage to operate.


I called last week to inquire about using this zone controller in a hangar that had a small office area and a large bay. I advised the call taker that I had Honeywell 9580. I also asked about the capability of the zone controller to handle the smaller office area’s lower CFM requirement and whether or not I could defeat the step-up from W1/Y1 to W2/Y2. I was told that the controller can be set up to defeat the stage step-ups.

After reading the manual, I found that there are no multi-stage inputs on the controller board from thermostats. So, basically, the capabilities of the Honeywell 9580 are wasted. Also, the stage defeat is for the whole system, not zone-specific as I need. It would be pointless to defeat stage increases while heating/cooling a large hangar space

ANSWER: The SmartZone controller typically controls staging based on the total system conditions which is the most efficient way to operate a multi-zoned multi-staged hvac system. However, the zone1 thermostat connector on SmartZone can be configured to allow the thermostat to control staging (refer to the top of page 10 of the installation manual). When the zone1 thermostat is configured for staging the ability to lockout 2nd stage with only 1 zone calling is disabled. With the thermostat controlling staging your ability to limit staging will be determined by the features of your Honeywell 9580 instead of the SmartZone control.


I have a honeywell mastertrol2 mm2, i wanted to update my thermostats but my zone controller has separate b and o wires going to thermostats . Will updating my zone controller to a smart zone 2 help this problem?

ANSWER: Updating your zone controller to a SmartZone 2 zone controller will allow you to use any 24VAC thermostat. SmartZone controls are designed to be universally compatible with 24VAC thermostats including WI-FI models used to control your thermostat remotely through the internet on your smart phone or tablet. You should be able to connect any 24VAC thermostat to a SmartZone control without any problems.


Do you have a digital thermostat that you recommend or sell to go with SmartZone?
From ecobee.com

From ecobee.com

ANSWER: ZoningSupply does not carry thermostats, however, SmartZone controllers are compatible with any 24VAC powered 5 or 6 wire thermostat. Popular brands our customers install with SmartZone include Honeywell, ICM, Braeburn, Nest, Ecobee, Aprilaire, Lux, Lyric,  and MANY others. We suggest you avoid using low priced 'power stealing' thermostats as they may cause intermittent issues if your utility power fluctuates. Power stealing thermostats are typically low priced and can be identified by the lack of a C (common) terminal on the thermostat wall mounting plate.
If you are looking for a WiFi thermostat check out this other article:

http://zoningsupply.com/blog/best-wifi-thermostat-for-zoning

SmartZone-2L
from $99.99

Check out the newest version here:
https://zoningsupply.com/buy/smartzone-2


2016: QUESTIONS from ONLINE CUSTOMERS

Support, homeownerszoning supplyComment

QUESTION: Will SmartZone replace Honeywell Trol-a-temp?

ANSWER: The SmartZone-4X is a "drop-in" replacement for all of the Honeywell boards.

Photo by spates/iStock / Getty Images

QUESTION: I live in Toronto, Ontario, Canada. Are there any qualified installers for the Smart Zone dampers?

ANSWER: Although we have customers in other parts of Canada, we do not have any specific HVAC contractor customers in Toronto. Any reputable HVAC contractor with previous experience installing zoning should be able to install the Ecojay SmartZone controls or dampers. Many do-it-yourself folks have also successfully installed Ecojay's controls/dampers without difficulty. If your contractor is not specifically familiar with SmartZone controls they can reach our technical support line, 844-ZONE-123, for assistance if needed. Feel free to contact us with additional questions.


QUESTION: I have an old DuroZone system (model SMZ-SW) that has stopped working and am looking for a replacement solution and have been researching the Smartzone option.  I have a few questions and wanted to see if you could help me.

  1. I'm not sure what has failed with the DuroZone system, but I wanted to first see if I replaced the controller with the Smartzone controller if it would work.  Will the Smartzone controller work with the DuroZone dampers ?
  2. Would you be able to put me in touch with an installer who could do the installation and testing of the smartzone controller ?  I'm not overly handy and would prefer a knowledgeable installer to do the install and tests.

ANSWER:

  1. Ecojay's SmartZone products are compatible with your current DuroZone controller.  Your existing thermostats and dampers are normally compatible with SmartZone.as well. Wiring the dampers into SmartZone may be different depending on the model dampers you have. We can provide damper wiring instructions when you or your installer inform us the damper models you have. 
  2. The change out of your existing Durozone controller should be simple for any competent hvac contractor even if they haven't used Smartzone before.  Zoning Supply can also be contacted for technical support toll free if you or the installer need technical assistance. 

QUESTION: I have a Honeywell Chronotherm 111 system with one main panel and three mercury thermostat controllers. I have been informed that my control panel is inoperative and three dampers have failed. I would like to upgrade the system with out
losing the capability/control of the temperature in each room. I am in dire need to correct/improve my system with the Honeywell product.

ANSWER: The Honeywell Chronotherm III thermostat (models T8600, T8601 & T8603) are 24VAC powered according to Honeywell's spec sheet and should be compatible with any Ecojay SmartZone controller.


QUESTION: My customer has a Carrier/Parker zone system, not sure what version. I want to replace the complete system minus the dampers. Currently there is a main controller, bypass controller and six zones. The bypass could be converted to a dump zone. Wireless is also an option. What do you think?

ANSWER:  From our knowledge of the Carrier-Parker controls, it is VVT control system  and Carrier released two generations of the product line that we know of.  One or both generations used dampers that had DC powered, multi-position actuators. Carrier has also tended to use a more proprietary control flow using a pulsed or multi-position damper actuator which do not have an internal stop switch.  SmartZone outputs 24VAC continuously on either the OPEN damper circuit or CLOSE damper circuit with the actuator using an internal stop switch to switch off power when it reaches stop in either open or close position. This is typical of most conventional residential/light commercial zone control brands and product-lines today. If your customer's current system does not match this specification you will need to change out the damper actuators if installing Ecojay SmartZone or any other major 24VAC brand control product. Ecojay's damper actuators have a torque rating of 18 in-lb/2 Nm and can work with a round or square shaft of 1/4" to 5/8" diameter.
SmartZone is expandable up to 20 zones, capable of 2C/3H stages and is compatible with any conventional 24VAC controlled equipment including heat pump or heat pump with dual fuel. SmartZone is also compatible with all off the shelf 24VAC thermostats. If you are able to supply the specific product model your customer is using I can probably be more specific about the compatibility issues.


SmartZone-4X
$299.00

This product is out of stock but can be replaced with the newest version SmartZone-4X 3.0

Click the link to see what is new!

QUESTION: I have a Honeywell Trol-a-temp Model MABS-2 422041-2 with a Mastertrol Add-a-zone model MAZ-1 TAT422027. This is a 4 zone electric system, heat pump with Emergency heat. I have the Master which control s the Emergency heat plus e thermostats. I would like to upgrade the Panel so that I can put a digital thermostat as the master.

ANSWER: SmartZone-4X will work for you.
http://zoningsupply.com/buy/smartzone-4x


QUESTION: I am looking to use this product with a 2 zone system that has 2 wire dampers. I have to power 4 dampers per zone. Will this produced do so? I am using 8" round dampers and there are 4 per floor.

ANSWER: All Ecojay SmartZone controls are compatible with 2 and 3 wire dampers. They can even be mixed on the same zone. SmartZone can support up to four 2 wire dampers (up to ten 3 wire dampers) on each zone.  Dampers and thermostats are powered from the SmartZone controller. It is important to determine the VA capacity of the transformer needed to power SmartZone as the number of devices powered from the controller increase. In your installation, the transformer used to power the SmartZone controller will need to support the power demand of the zone controller (12VA), 8 dampers (2-wire dampers at 7-10VA each), and 2 thermostats (2VA each). Total potential transformer VA demand from these components collectively total 96VA (12+80+4). However, assuming your 2 wire dampers are power close/spring open, power demand from the dampers will occur only when the dampers are closed. With a 2 zone system, you will never see both zones closed at the same time (all dampers default to open when no zones are calling) so your maximum power demand will be only from 4 dampers. This changes the maximum potential power demand to 62VA (12+40+4). A 75VA - 24VAC transformer will be capable of providing adequate power for your system. This size transformer is readily available on Ebay and many other web stores.  If your 2 wire dampers are power open/spring close (this type is typically used only for fresh air ventilation) then you will need a transformer with a VA capacity of 100VA minimum.  Visit our zoningsupply.com website and review the ZS2X/4X installation guide for more information on installation. Thank you for contacting Zoning Supply with your question. We appreciate your interest in our SmartZone products.


QUESTION: The 9580 thermostat uses delta T (difference between actual room and called for temps) as part of the staging calculation.  If the staging function of the thermostat is replaced by the zone controller, how does the controller get delta T, or is is not used?  If not, ow does it determine staging...is it rate of temp change sensed by the probe?

ANSWER: SmartZone uses algorithms based on time and supply air temperature (as measured at the supply air plenum) to control staging. Each time the equipment is started SmartZone will require a minimum run time in stage 1 before it will consider staging. This initial run time allows for the equipment to achieve a stable temperature in heat or cool before determining if staging up is necessary. After the initial run time requirement is achieved SmartZone compares supply air temperature to the cut-in temperature settings and will stage up if conditions are met. When the equipment is running stage 2 SmartZone will compare supply air temperature to the cut-out temperature and will return to stage 1 if conditions are met. SmartZone staging algorithms will vary the time and temperature elements based on equipment type (gas/electric or heat pump) and mode of operation (cool or heat). The SmartZone Installation manual included with your product provides detailed information about the sequence of operations for adjusting staging settings including the specific algorithms used for each equipment type and their modes of operation.

 

SmartZone on TV - Greenovate Episode: Austin, TX

homeownerszoning supplyComment

I believe this first aired in 2006 - making this system at least 10 years old.  I have made contact with the homeowner through the original installer and it turns out that it is still working great.  Since then, they have upgraded to NEST thermostats but nothing else has changed.  They are considering upgrading the equipment to higher efficiency stuff that is available now but still want to keep SmartZone in place.

Wireless or Wifi Thermostats... What's the difference?

homeowners, Products, thermostatsWhitney PitzerComment

Despite often being used interchangeably, wifi and wireless thermostats refer to 2 very different types of devices.

Wifi stats (like the Nest or Ecobee) have surged in popularity over the last few years. Wireless stats have actually been around for a quite a while but are not quite as popular. Both types of devices perform the same basic function of controlling your heating and cooling unit as the room’s temperature changes. Both can be programmable and have touch-screens. Both can help you reduce energy consumption, especially when paired with a zoning system like SmartZone.

Key Differences:

Wireless thermostats can essentially be placed anywhere in your home. Think of it like a remote control for your HVAC. They do not need to be WIRED to the wall or to the HVAC unit.

WiFi thermostats are not wireless and are generally wall-mounted. They enable users to control the thermostat remotely from a phone, computer, or tablet. In some areas, even the local energy companies can request access to your wifi stat.

The differences are as simple as their names imply. Wireless stats operate without being wired to the wall or system. Wifi stats are stationary, but can be controlled from peripheral devices.

Benefits:

A person in the market for a wireless thermostat is looking for a device that can be placed anywhere in the home and not necessarily on a wall.

A person in the market for a wifi thermostat is looking for the ability to control their thermostat from anywhere. They might also be looking for the benefits that come with having your stat connected to the internet. Some top of the line wifi thermostats can display weather info, news headlines and more. They can also integrate with various home-automation systems.

After looking at the benefits of the 2 types of devices, it’s easy to see why wifi thermostats have out-paced wireless thermostats in popularity. However, both inventions are remarkable examples of how the HVAC industry is racing forward to meet the comfort and convenience requirements of 21st century homes and buildings. 

For more information about innovative thermostats and HVAC energy-efficiency, visit:

www.zoningsupply.com

http://www.gadgetreview.com/6-of-the-best-wifi-thermostats

www.ecobee.com

www.nest.com